PBO-MRTU: Modbus Single & Three Phase Voltage Monitor

Voltage Ranges:
• 115 to 277VAC, 1Ø
• 200 to 600VAC, 3Ø
Self-Powered
21 Built-In Voltage Selections
All Settings are Read/Write
Data is Communicated via ModbusRTU
Power and Communications Status LED
Operation
The PBO-MRTU monitors 21 single and three phase voltages and tolerances pre-programmed into the PBO and communicates all of the voltages, set-points and faults via ModbusRTU. All voltages and setting address are available as read/write. There is no output relay in the PBO-MRTU.
The Modbus addresses are downloadable at www.rke.com/downloads
The LED operations are as follows:
Continuous green LED – The PBO-MRTU has power
Green Flashing LED – The PBO is detecting communications on the Modbus network
Red Flashing LED – The PBO-MRTU is transmitting data on the Modbus network
Specifications
Electrical
Line Voltage: 115 to 277VAC, 1Ø
200 to 600VAC, 3Ø
Supply Voltage: 12 to 24 VAC/VDC
Frequency: 45 to 65 Hz
Over/Under Voltage: 3% to 15%
Phase Imbalance: 3% to 15%
Phase Rotation: A - B - C
Time Delays:
Trip Time: 1 Sec. to 10 Sec. @ ±20%
Re-Start: 1 Sec. to 5 Min. & Manual Reset
LED:
Power: Continuous Green
Transmitting Data: Flashing Red
Communications on Network: Flashing Green
Power Consumption: 1VA
Physical
Mounting: Surface or DIN
Termination: Pluggable Terminal Block
Packaging: Epoxy Fill
Weight: 5 Ounces