CSB: One Shot Plug-In Timer
• Digital CMOS Design
• 10 Amp, DPDT
• ±0.2% Repeatability
• Transient Protected
• Timing Ranges Up to
24 Hours
Operation
One Shot
When input voltage is available, closure of the customer supplied contact (C1) will energize the internal relay and begin the timing cycle. At the end of the timed period, the relay will be de-energized. Closure of the contact (C1) may be maintained, momentary or repeated. The relay will only remain energized for the time period initiated by the initial closure of the contact. The CSB resets when timed cycle is complete with the contact open or the input voltage is removed.
Specifications
Electrical
Input Voltage:
24 or 115VAC, ±10%, 50/60Hz
24 or 110VDC ±10%,
Filtered to Full Wave.
Time Delays:
Type: Adjustable or Factory Fixed
Range: 50 Milliseconds to 24 Hours
Repeat Accuracy: ±0.2% of Time Range or
±10Milliseconds, Whichever is Greater
Fixed Time Accuracy: ±5% Worst Case
Control Contact Response Times:
Start Timing: 50 Milliseconds, Typical
After Timing: 50 Milliseconds, Typical
Protection: Varistor and/or R-C Network
Power Consumption: 5VA
Output Relay:
10 Amps @ 120/240VAC
500,000 Full Load Electrical Cycles
50,000,000 Mechanical Cycles
U.L. Ratings:
6.5 Amps, 1/3 HP, 125VA @ 240VAC
7 Amps, 1/6 HP, 125VA @ 120VAC
Physical
Mounting: Plug-In
Termination: 8 or 11 Pin & Blade Base
Packaging: Dust Cover
Weight: 7 Oz.
Ambient Temperatures
Operating: -10°C to 65°C
U.L. Operating: -10°C to 40°C
Storage: -10°C to 85°C