DPM: Digital Multi-Range Three Phase Voltage Monitor
Voltage Ranges:
• 115 to 277VAC, 1Ø
• 200 to 600VAC, 3Ø
Digital Display:
• Line Voltages
• Frequency
• Imbalance %
• Output Relay Status
• Last 4 Faults
• Set-Up Menus
SPDT & 1NO Contacts
Operation
The DPM is a Digital Phase Monitor that will monitor line voltages from 200VAC up to 600VAC. Actual line voltages and set-up parameters are set via the digital display. The supply voltage must be available during operation. With the supply voltage active, you can set-up all of the DPM’s settings without the line voltage connected.
When the DPM is connected to the line voltage, it will monitor the line and if everything is within the set-up parameters, the output contacts will be activated. If the line voltages fall outside the set-up parameters, the output relay will be de-enegized after the trip delay.
Once the line voltages recover, the DPM will re-energize the output relay after the re-start time delay (manual to 4 minutes).
All settings and the last 4 faults are retained, even if there is a complete loss of power.
Specifications
Electrical
Line Voltage: 115 to 277VAC, 1Ø
200 to 600VAC, 3Ø
Supply Voltage:
12VDC, 24VDC, 24VAC, 120VAC & 240VAC,1Ø
Frequency: 50/60Hz
Display:
16 Character, 2 line, LCD back lighting
Adjustments:
Membrane Buttons & Display
Nominal Voltage: Adj. 200 to 600VAC
Over/Under Voltage: Adj. 7% to 15%
Phase Imbalance: 3% to 10%
Phase Rotation: A - B - C
Delays:
Trip Delay: Adj. 2 sec. to 10 sec.
Re-Start Delay: Adj. Manual Reset to 4 min.
Power Consumption: 2.1VA
Output Rating @ 25°C:
10 Amps @ 120VAC
6 Amps @ 277VAC
1/8 HP @ 120/277VAC
5 Amps @ 30VDC
Physical
Mounting: Surface Mounting (2 screws)
Termination:
Line Side: 1/4” Push-On Tabs
Control Side: 0.187” Push-On Tabs
Packaging: Dust Cover & Epoxy Fill
Weight: 1 Pound
Ambient Temperatures
Operating:
T - Tabs -40°C** to 65°C
B - Terminal Blocks -40°C** to 59°C
**Display & membrane may not function below -20°C.
Storage: -40°C to 85°C