MGS: Off Delay Solid State Timer
• Low Cost
• 1 Amp Output, 1NO
• Fixed or Adjustable Delays
• Screw Terminals or
Push-On Tabs
• Voltages from
24 to 220 Volts
• Epoxy Filled
Operation
Off Delay
When input voltage is available, closure of the customer supplied contact (C1) will energize the load. When the contact is opened, the timing cycle begins. At the end of the timed period, the load will be de-energized. Re-closure of the contact during the timing cycle will reset the timer. The MGS also resets when the timed cycle is complete or the input voltage is removed.
Specifications
Electrical
Input Voltage:
24 to 220V, ±10%
Frequency:
AC - 50/60Hz
DC - Filtered to Full Wave
Time Delays:
Type: Adjustable, Factory Fixed or Remote
Range: 100 Milliseconds to 5 Minutes
Repeat Accuracy: ±1% with Fixed Conditions
Reset Times:
During Timing: 70 Milliseconds, Typical
After Timing: 150 Milliseconds, Typical
Protection: Varistor and/or R-C Network
Power Consumption: 5VA
Output Ratings:
Type: Solid State
Form: One Normally Open (1NO, Form A) Non-Isolated
Rating: 1 Amp Continuous @ 25°C
Resistive: 100%PF
Inductive: 75-80%PF
15 Amps Inrush, Non-repetitive
30 mAmps to ensure Turn-on
Physical
Mounting: Surface, #6 Screws
Termination: Screw or .25” Push-On Tabs
Packaging: Epoxy Filled
Weight: 4 Oz.
Ambient Temperatures
Operating: 0°C to 65°C
Storage: -30°C to 85°C
Notes:
Remote Timing Resistors—multiples of 2.7 megohms will increase the time delay by 1 minute ±20%.
For adjustment codes 3 & 4 a jumper or resistor must be installed across terminals 5 and 6 to allow the timer to time out.