top of page

RCS5: Single Phase 480VAC Transient Voltage Filters

RCS5A-30_edited.jpg

• 480 Volt Ratings

 

• Single Phase (1Ø)

  Applications

 

• Varistor Options

 

• Stranded Wire Leads

Operation

Transient Voltage Filters

R-C networks (Resistance-Capacitance) are applied to circuits where transient electrical voltages can cause a malfunction or damage in solid state controls or control systems (PLCs, CNCs, NCs, Solid State Counters, etc.) The RCSs are typically applied in parallel with single phase inductive loads (motor starter coils, contactor coils, solenoid valves, etc.) to absorb the transients generated when the load is de-energized.

 

Specifications

Electrical

Input Voltage: Up to 240VAC, 1Ø, 50/60Hz.

Capacitance: 0.47 microfarads, ±10%

Resistance: 22 to 680 ohms, ±10%, 0.5 watt

Varistors:

Voltage Code / Max. Allowable AC  /  Max. Clamping  / Energy (Joules)

    1    /    130VAC     /    340V @ 10A     /    10

    2    /    130VAC     /    340V @ 10A     /    10

    3    /     250VAC    /    650V @ 10A     /    17

    7    /     150VAC    /    395V @ 25A     /    25

Power Consumption: 10VA @ 240VAC

 

Physical

Mounting: Surface

Termination:

     #18 Stranded Wire Leads or

     #20 Solid Wire Leads

Packaging: Epoxy Filled

Weight: 1 Oz.

 

Ambient Temperatures

Operating: -40°C to 85°C

Storage: -40°C to 85°C

 