TDR: Universal Function Relay
• 24 to 240VAC/VDC
(Universal Voltage)
• Multiple Functons
• Time ranges up to
24 hours
• Pulse Frequencies
• Adjustment Knobs
• Plug-In Package
• DPDT Contacts
• Status LEDs
Operation
The TDR series of electronic relays is a processor based control that can have many different functions. The operation of the TDR is determined at the time of manufacture, based on the firmware loaded into the relay.
Special functions (X) that are unique to a customer’s specific application are available by contacting the factory.
Functions available include:
C - On Delay (Delays to turn On)
D - Interval On (Turns On and then times out)
F - Off Delay (Turns on then delay turning Off after loss of signal)
L - Pulse Frequency (Supplies prox power on monitors pulse frequency)
R - Repeat Cycle (On & Off & On & Off etc.)
S - One Shot (One output per input)
U - Universal (Multiple functions and time ranges)
Specifications
Electrical
Supply Voltage:
24 to 240VAC/VDC
Frequency: 50 to 400Hz
Prox Supply: 15 mAmps @ 12VDC
Frequency Range: 0.1 to 200PPS
Sensor Type: Prox or Contact
Signal Input: Sourcing (PNP)
Pick-Up/Drop-Out Delay: 0.5 Sec
Time Ranges: 0.1Sec. up to 24 Hrs.
Remote Pot: 1KΩ to 20KΩ (Max.)
Power Consumption: 1.5VA
Indicators: 2 LEDs
Output Rating @ 25°C:
5 Amps @ 250VAC (General Purpose)
1/8 HP @ 120VAC
5 Amps @ 30VDC
B300 (Pilot Duty)
360 VA
3 Amps @ 120VAC
1.5 Amps @ 240VAC
Physical
Mounting: Plug-In
Termination: 8 or 11Pin
Packaging: Dust Cover
Weight: 8.5 Oz. Approx.
Ambient Temperatures
Operating: 0°C to 65°C
Storage: -40°C to 85°C
Notes:
On MRS with remote timing resistors, multiples of 2.7 megohms will increase the time delay by 1 minute ±20%.
For adjustment codes 4 a jumper or resistor must be installed across terminals 5 and 6 for the On Time and Terminals 7 & 8 for the Off Time to allow the timer to time out.