ZVR/S: Zero Speed Switch ZVR ZVS
• 35mV to 430mV AC/DC
• 600V Overvoltage
• 10 Amp, SPDT
• Noise Filter
• Adj. Sensitivity
• Adj. Time Delay
• Normal or Reverse
Operation
• Din or Surface Mount
• Plug-In Terminal Block
Operation
An AC supply voltage must be provided to the ZV continuously. While the ZV will drop-out and pick-up based on an adjustable millivolt set point, the signal circuit will accept up to 600VAC or DC. With no voltage on the signal terminals, the internal relay is energized, transferring the output contacts. When the voltage exceeds the set point, the relay will de-energize. When used on Zero Speed applications, a loss of input voltage will cause the relay to remain de-energized as if the motor were still running. Reverse operation is available. For DC current sensing, select a 100mVolt shunt of the correct current rating and connect the shunt in series with the load and in parallel with the ZV’s signal terminals.
Specifications
Electrical
Supply Voltage: 24 to 240 VAC, ±10%, 2W
Sense Ranges:
DC Sensitivity: 35mV to 430mV
AC Sensitivity: 38mV @ ≤6Hz, Typ. 380mV @ ≥60Hz, Typ. Hysteresis: 5% of set point, AC/DC typical
Signal Impedance: 100KΩ minimum
Time Delay:
1 sec.Fixed or 0.5-40 sec. Adjustable
60 Hz Rejection: 10 times DC Sensitivity at most sensitive setting.
Frequency: DC to 400 Hz
Max. Continuous Sense Voltage: 600 Volts, AC or DC
Output Rating:
Resistive: 10 Amps@240VAC
V-A Rating: 180VA Max. Rating Code: C300
Physical
Mounting: Din Rail or Surface, #6 Screw
Termination: Plug-In Terminal Block
Packaging: Vertical Case
Weight: 8 Oz.
Ambient Temperatures
Operating: 0°C to 65°C
Storage: -40°C to 85°C